Requirements on maintenance and application |
1. |
Operating environment:The temperature in the room to be laid with antistatic floorings sh-
all be 15°-35°C and the relative humidity is 45% - 75%.If the humidity of computer rooms
is low for a long time,there may be cracks on the floor sur face and the strength and thi-
chness of attaching veneer shall be increased therefore. |
2. |
Maintenance requirements: |
|
|
| |
(1)It is forbidden to directly use sharp tools to carry out construction on the floor sur-
face in order to avoid the damages to the appearance and antistatic performance of floor-
ing surface; |
| |
(2)During application, no person is allowed to jump onto the floor from high position, and
it is forbidden to crudely remove equipment as such iperation may damage the floor; |
| |
(3)When equipment is moved on access floor, it is forbiden to directly pull the equipment on floor as it may scuff the floor;the equipment shall be lifed before moving; |
| |
(4)When heavy equipment is to be installed in machine room,it shall be directly placed on base frame;i.e. it is forbidden to directly place the heavy equipment on floor as deformation may be saused by long-term load bearing; |
| |
(5)To repair the equipment under floor, board sucker shall be first used to remove floor-
ing;it is forbidden to use sharp tools to crudely dismantle and assemble the flooring; |
| |
(6)Dring maintenance,dust collector or mop can be used to keep the floor clean. Particul-
arly,measures shall be taken to avoid sprinkling liquid ont floor; |
| |
|
| |
|
|
|